T200 series UPS   
     
 
Tescom 200 Series are, True Online, Double Conversion UPS Systems, manufactured with the state of the art,PWM and IGBT technology,
 
producing microprocessor controlled pure sinewave output to critical loads
FEATURES:
Galvanic isolation transformer at the inverter output
Efficiency up to 91 %
Static by-pass
LCD panel providing detailed information
64 recorded event history
RS232 and dry contacts for comunication and remote monitoring
Input/output customization, possible
Compatible with international standards
1 year full warranty
Supply of spare parts guaranteed for over 10 years
Designed and manufactured under TUV-ISO9001 certification
 
 
200 SERIES UPS
MODEL 206 207 210 215 220 230
Power (kVA) 6 7.5 10 15 20 30
INPUT
Voltage 230/400 Vac 3 phase +N,+/-15%
By-pass Voltage 230 Vac, +/- 10%
Current 3 x 13A 3 X 16A 3 X 21A 3 X 31A 3 X 42A 3 X 62A
Input frequency 50 Hz, +/- %15
EMI EN50091-2 Class A.
Input out of tolerant protection electronic input out of tolerant protection
OUTPUT
Power (kW) 4,2 5,25 7 10,5 14 21
Power factor

0,7

Voltage

230 Vac, +/- 1%

Frequency 50 Hz (60 Hz on request)
Frequency tolerance +/-2% (line synchronized)
+/- 0,2% (free running)
Efficiency at 100% load 86-90%
Crest factor 3:1
Overload protection 100%125% load :10 min
125%150% load :1 min
<150% load : by pass
Short circuit protection Electronic short circuit protection
Voltage out of tolerant protection Electronic out of tolerant protection
Total harmonic distortion (THD) <3%
Communication Dry contacts & RS232
BATTERIES
Type Sealed Lead Acid - Maintenance free
Number of Batteries 20 26
Float Charging Voltage 270 VDC 351 VDC
End of discharge voltage 200 VDC 260 VDC
Battery cabinet Internal External Internal
Battery ambient temperature C 25 C
Battery protection Automatic circuit breaker
Battery out of tolerant protection Electronic battery out of tolerant protection
Battery test Optional Automatic every 72 hrs
GENERAL
MODEL 206 207 210 215 220 230
Human interface 2x16 character LCD panel
Communication RS232+DRY contacts
Software T-Mon UPS Management Software (3 clients standart)
Overtemperature protection Electronic overtemperature protection
Temperature range 0 C - 40 C
Relative humidity(non condensed) 90% max
Protection degree IP20
Altitude < 1000 m above sea level
Acoustic noise <50 dBA <55 dBA
Weight without Batteries (kg) 106 110 125 135 277 300
Dimensions (mm) HxWxD 950x265x740 710x265x740 1360x550x855
OPTIONS
Input transformer Galvanic isolation transformer at the input
Input THD * <10%(with 18 Pulse Rectifier) Except 206 & 207
<5% (with 18 Pulse rectifier, + filter) Except 206 & 207
Input Power Factor * 0.95 - 0.98 (with 18 Pulse rectifier)
MBS Maintenance by-pass switch for complete isolation (For 206,207 & 210)
Parallel operation 1+3 Systems (hot standby, reduntant, symetric parallel)
(*): In some 18 pulse applications, the standard chasis dimensions may change.
 ACCESSORIES
Monitoring and control software TMON 3 clients standart
LCD Remote monitoring panel Available as option
Graphical remote monitoring panel Available as option
Multiserver shutdown unit Available as option
SNMP communication adaptor Available as option
MODBUS communication adaptor Available as option (over RS485 or over TCP/IP)
Serial Port enhancer Available as option
Long distance RS232/485 adaptor Available as option