3 Phase static transfer switch

 

     
 
Tescom STS's(Static Transfer switch) are designed to transfer the supply between two independent AC power sources, it monitors two input source and if one fails it will automatically transfer the load to the other source.
 
TESCOM STS MAIN FUNCTIONS:
Increased power quality
Increased noise reduction
Power blackout protection
Power redundancy
Automatic static switching
Remote monitoring input power sources
Easy static and mechanical transfer to input sources
Remote management the power events
Power event logging
UPS redundancy
 
 

 

3 Phase static transfer switch
MODEL STS325 STS350 STS3100 STS3150 STS3200

INPUT

Voltage 230/400 Vac 4 wires
Input voltage analog error window adjustable
Blackout error window adjustable
Frequency 50 Hz or 60 Hz, +/- %-5
Input frequency error window adjustable
Voltage distortion <%10
Phase balance error sense offset adjustable

OUTPUT

Current 25A 50A 100A 150A 200A
Voltage 230/400 Vac 4 wires
Frequency 50 Hz or 60 Hz, +/- %-5
Overcurrent inhibit LCD front panel,MBP standard
Load crest factor upto 3.5
Protection SCR protection and overcurrent protection available
AC/AC efficiency >%98
Load PF range 0.6 lag to 0.9 lead

GENERAL

Dry contacts 7 dry contact outputs
Switched neutral optional
Type of transfer break before make
Transfer time <5 msec within CBEMA & IEEE for synchronized sources
<11 msec for unsynchronized sources
Overload 150% for 15 min, 1000% for 40 msec
Cooling two fans(reduntant)
Standards EN50091-2 class A ISO9001
Communication >Advanced RS232
Cabinet interior temperature sensor >available
Ambient temperature 0 - 40 ºC
Humidity 0 - 95%(non condensed)
Dimensions(WxDxH) 570x500x1415
FEATURES:
Easy monitoring all parameters on LCD display
FAst microcontroller 32 mips
Password protected login system from remote site (timed Access)
Two redundant power supplies for boards(hot swap)
Easy front access to all components inside of the STS
Second protection cover on live circuits which prevent electrical shock
Input sources protected by fuses
Three positioned maintenance by-pass switch which prevents cross currents between input sources
All parameters can be adjusted by the user with a password
Real time clock built in
Alarm history(with date and time)
Automatic transfer test from remote site or front panel
Front panel lamp test
External emergency shutdown(EPO) input
Hot plug construction during maintenance by-pass
High current output tolerant upto 1000%
Adjustable long dead time during nonsynchron transfer up to 3 seconds
SCR fault sense circuit built in
Fast voltage black out circuit
Input phase balance circuit
Output alternance balance circuit
Adjustable input source frequency lower/upper limit
Additional analogue synchron sense circuit